1. System Settings
Input Voltage (AC) | 250 – 470 VAC, 50 Hz |
On voltage (Cold Start) | 250 VAC |
Auto Off voltage | 200 VAC |
2. Protections / Setting Parameters
Protection Design | Voltage and Current Sensing |
Thermal Overload Range | 1.5-2.5 / 2.5-4 / 4-6.5 / 6-10 / 9-14 / 13-21 Amps. |
Sr. No. | Parameter | Setting Range | Default setting | Trip Time Delay | LED |
---|---|---|---|---|---|
1 | Phase Failure | Fixed | Fixed | 4 sec ± 1 sec | YES |
2 | Reverse Phase | Fixed | Fixed | 4 sec ± 1 sec | YES |
3 | Voltage Unbalance | Fixed | Fixed | 4 sec ± 1 sec | YES |
4 | Thermal Overload | As per Relay | As per Range | NA | NO |
5 | Dryrun | 60% – 95% | < 75 % | 15 sec | YES |
3. Timers
Sr. No. | Parameter | Setting Range | Default setting |
---|---|---|---|
1 | Power on Timer | Fixed | 60 sec ± 3 sec |
4. Monitoring
Analog Voltmeter | 200 – 500 V |
Analog Ammeter | 1 – 30 Amp. |
5. Reset
Resetting mode | By Reset switch |
6. Output Relay Contact
Relay Mechanical life | 10 lac operations |
Dielectric Strength | 2.2 KV , 50 Hz for 1 min |
7. Enclosure & Mounting
Enclosure Material | Rust proof, Shock Proof, Powder Coated Metal Enclosure |
Mounting | Wall Mounting with 4 screw M4 × 15 mm |
Temperature | 5 to 60°C |
Humidity | Up to 90% RH |
8. Dimensions & Weight
L × W × D (mm) | 290 × 262 × 105 mm |
Power Consumption | Less than 5 Watts |
Weights | 2989 gms. |